Punching Shear Checker (ACI 318-19)

Check two-way shear around a column in a flat slab or raft – interior, edge or corner – with unbalanced moments in both directions, and design stirrups if needed.

ACI 318-19 22.6Table 22.6.5.2 λs8.4.4.2 γv8.6.1.2

By Eng. Anwar Ali Khan, MSc (Structural), PE – Civil & Structural Engineer (SCE member) · Version 1.0 (draft) · Last reviewed: 15 Nov 2026

Draft – under verification. Results are being cross-checked against hand calculations and verified spreadsheets. An engineer must check all results before use.

Results

Code checks

    Drawing (live)

    Table

    Step-by-step working

    ItemCheck / formulaValueReference
    Did this tool help?

    How the check works

    The critical section is taken at d/2 from the column faces (22.6.4.1): four sides for an interior column, three for an edge column and two for a corner column. The factored shear stress combines direct shear Vu/(bo·d) with the part of the unbalanced moment transferred by eccentric shear, γv·Mu·c/Jc, in both directions (8.4.4.2.3). γv = 1 − γf, with γf = 1/(1 + (2/3)√(b1/b2)). The concrete capacity is the least of the three expressions in Table 22.6.5.2, multiplied by the new size-effect factor λs.

    ACI 318-19 changes

    Worked example

    Interior 500 × 500 column, 250 mm slab (d = 210 mm), f′c 35 MPa, Vu = 650 kN, Mu1 = 60 kN·m, Mu2 = 30 kN·m. b1 = b2 = 710 mm, bo = 2840 mm, so vuv = 650 000/(2840 × 210) = 1.090 MPa. With γv = 0.40 and Jc = 5.12 × 10¹⁰ mm⁴, the moment terms add 0.166 + 0.083 MPa, giving vu = 1.340 MPa. λs = 1.0 (d < 250 mm), vc = 0.33√35 = 1.952 MPa, φvc = 1.464 MPa ≥ 1.340 MPa: OK without shear reinforcement (92% used).

    Limits

    FAQ

    Which direction is "direction 1"?

    Direction 1 is along c1. For an edge column, direction 1 is perpendicular to the free edge, so Mu1 is the moment that bends the slab towards the edge.

    Why do edge and corner columns fail more often?

    They have a shorter perimeter (bo), a smaller αs and usually larger unbalanced moments, so both the demand is higher and the capacity is lower.

    Can I use ETABS/SAFE moments directly?

    Yes – use the unbalanced moments transferred to the column at the slab level for the governing load combination, together with the column reaction Vu.